Title of article :
Influence of plates on flow inside a recessed space generated by rejected heat
Author/Authors :
M. Bojic، نويسنده , , F. Yik، نويسنده , , M. Lee، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Pages :
12
From page :
593
To page :
604
Abstract :
In this paper, we report investigations into temperature and flow field inside a recessed space outside a high-rise residential building in Hong Kong. The investigated 30-story recessed spaces contain 30 air-conditioners, and one or two horizontal plates. We studied the worst-case scenario in summer when all air-conditioner units reject condenser heat into this space. The predictions by using FLUENT 5.0, a computational fluid dynamics code, show that presence of one plate inside the space would cause the overall excess temperature at condenser entrance to fall up to 30%. The presence of two plates would make this figure to be around 40%.
Keywords :
Air-conditioners , Heat rejection , High-rise residential buildings , Recessed spaces , Temperature rise
Journal title :
Building and Environment
Serial Year :
2003
Journal title :
Building and Environment
Record number :
408627
Link To Document :
بازگشت