  • Abstract
    We performed the experimental and the numerical studies on thermal comfort (TC) and indoor air quality (IAQ) in the lecture room with cooling loads when the operating conditions are changed. Predicted mean vote (PMV) value and CO2 concentration of the lecture room were measured and compared to the numerical results. Both of them showed a reasonable agreement with each other and then we applied the numerical model to analyze TC and IAQ for a couple of different operating conditions. From the results we found that the increment of the discharge angle of 4-way cassette air-conditioner makes uniformity of TC worse, but rarely affects IAQ. It turned out that TC and IAQ are hardly affected by the variation of the discharge airflow. Finally TC was merely affected by the increment of the ventilation rate, but when the ventilation rate is more than 800 m3/h, the average CO2 concentration can be satisfied with the standard limits of Japanese in our case studies.
  • Keywords
    Indoor air quality (IAQ) , Predicted mean vote (PMV) , 4-way cassette air-conditioner , Thermal comfort (TC) , Carbon dioxide (CO2)