Title of article :
Practical cooling capacity estimation model for a suspended metal ceiling radiant cooling panel
Author/Authors :
Jae-Weon Jeong، نويسنده , , STANLEY A. MUMMA، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2007
Pages :
10
From page :
3176
To page :
3185
Abstract :
The main thrust of this research was to develop a simplified cooling capacity estimation model for a suspended (free-hanging type) metal ceiling radiant cooling panel. By statistically analyzing panel performance data generated by a validated analytical panel model, the impact of various design parameters and their combinations on the panel cooling capacity was estimated. And then a linear regression equation was derived as a function of major design parameters and interactions which have significant effects on the panel capacity. In this analysis, eight single parameters and 13 two-factor interactions showed significant impact on the panel cooling capacity. Consequently, a simplified regression model for a free hanging panel was derived as a function of those selected parameters. The proposed model could estimate the panel cooling capacity not only for the natural convection but also for the mixed convection condition present in a mechanically ventilated space.
Keywords :
Ceiling radiant cooling panel (CRCP) , mixed convection , Radiant panel cooling capacity , Free hanging ceiling , Suspended ceiling
Journal title :
Building and Environment
Serial Year :
2007
Journal title :
Building and Environment
Record number :
409584
Link To Document :
بازگشت