Title of article :
Risks of unsatisfactory airborne bacteria level in air-conditioned offices of subtropical climates
Author/Authors :
K.W. Mui، نويسنده , , L.T. Wong، نويسنده , , P.S. Hui، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Abstract :
Adjustment of the indoor air temperature and relative humidity set points for energy conservation is adopted in many air-conditioned offices in the subtropics. This study examines the environmental risks in an air-conditioned office with a ‘readjusted’ thermal environment from the perspective of the probable airborne bacteria level exceeding certain limits. In particular, a cross-sectional study of bacteria concentrations in 422 air-conditioned offices in Hong Kong was conducted, and a mathematical expression was proposed to correlate the indoor bacteria level with the indoor air temperature and relative humidity in an air-conditioned office. With the proposed correlation, the probability of an air-conditioned office having an unsatisfactory airborne bacteria level could be determined. The model results were verified with the measurement results from some other studies. This model would be a useful tool for preliminary assessment of the environmental risks, regarding the airborne bacteria level while balancing some energy conservation measures, in an air-conditioned office in the subtropics. The study also provides a template for developing an environmental risk assessment model in air-conditioned spaces elsewhere.
Keywords :
Air-conditioned offices , Airborne bacteria level , temperature , humidity
Journal title :
Building and Environment
Journal title :
Building and Environment