Title of article
Indoor air-quality control by a fuzzy-reasoning machine in naturally ventilated buildings
Author/Authors
A. I. Dounis، نويسنده , , M. Bruant، نويسنده , , G. Guarracino، نويسنده , , P. Michel، نويسنده , , M. Santamouris، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
18
From page
11
To page
28
Abstract
This paper investigates the performance of a fuzzy reasoning machine for the control of indoor air quality in naturally ventilated buildings. Simulations have been performed using a new airflow and pollutant transport model, which has been developed and validated for this purpose; CO2 concentration was used as the indoor-air quality (IAQ) index for these simulations. Results have shown that satisfactory IAQ levels can be maintained, while good stability of the control parameter (i.e. window opening area) was achieved. The impact of such a controller on indoor-air temperature was also studied. The performances were not as good as expected, but were not negligible when compared with the normal conditions of use of the building.
Journal title
Applied Energy
Serial Year
1996
Journal title
Applied Energy
Record number
414179
Link To Document