Title of article :
Simplified model for indirect-contact evaporative cooling-tower behaviour
Author/Authors :
Pascal Stabat، نويسنده , , Dominique Marchio، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
A simplified model for indirect cooling towers behaviour is presented. The model is devoted to building simulation tools and fulfils several criteria such as simplicity of parameterisation, accuracy, possibility to model the equipment under various operation conditions and short computation time. On the basis of Merkelʹs theory, the model is described by using the Effectiveness-NTU method. The model introduces only two parameters, air-side and water-side heat-transfer coefficients which can be identified from only two rating points, data easily available in manufacturersʹ catalogues. Thus, the model allows one to estimate energy and water consumptions under different operating conditions such as variable wet-bulb temperatures or variable airflow rates.
Keywords :
Closed cooling tower , heat and mass transfer , Modelling , Air conditioning , Variable air-flowrate , Water consumption
Journal title :
Applied Energy
Journal title :
Applied Energy