Title of article :
Cycle analysis of air-cooled absorption chiller using a new working solution
Author/Authors :
Jung-In Yoon، نويسنده , , Oh-Kyung Kwon، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Pages :
15
From page :
795
To page :
809
Abstract :
A cycle analysis was achieved to predict the characteristics by comprehensive modelling and simulation of an air-cooled, double-effect absorption system using the new H2O/LiBr+HO(CH2)3OH solution. The simulation results showed that the new working fluid may provide the crystallisation limit 8% higher than the conventional H2O/LiBr solution. With a crystallisation margin of 3 wt%, the optimal solution distribution ratio was found to be in the range of 37–39%. Variation of cooling air inlet temperature had a sensitive effect on the cooling coefficient of performance (COP) and corrosion problem. The simulation of heat exchangers with UA value revealed that the absorber and evaporator were relatively important for an air-cooled system compared with the condenser and the low temperature generator. The effects of cooling air flow rate, circulation weak solution flow rate and chilled water inlet temperature were also examined. The new working fluid may provide a COP approximately 3% higher than the conventional H2O/LiBr solution in normal conditions of circulation weak solution.
Journal title :
Energy
Serial Year :
1999
Journal title :
Energy
Record number :
416003