• Title of article

    Energy consumption analysis on a dedicated outdoor air system with rotary desiccant wheel

  • Author/Authors

    Weiwei Liu، نويسنده , , Zhiwei Lian، نويسنده , , Reinhard Radermacher، نويسنده , , Ye Yao، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2007
  • Pages
    12
  • From page
    1749
  • To page
    1760
  • Abstract
    A dedicated outdoor air system (DOAS) with rotary desiccant wheel is the combination of a desiccant dehumidification system and a vapor compression refrigeration system. An energy consumption model of this hybrid DOAS is established for its analysis. Coefficient of performance, COP, is appropriately defined for evaluation on performance of the hybrid DOAS. The results indicate that, compared with a conventional DOAS, energy savings are possible for the suggested DOAS, when solar energy or natural gas is used for regeneration. Ventilation air flow rate, temperature or humidity of outdoor air, as well as regeneration-to-process air ratio, influence the energy consumption and the COP of the hybrid DOAS, greatly.
  • Keywords
    Dedicated Outdoor Air System , energy consumption , Hydrid , Rotary desiccant wheel
  • Journal title
    Energy
  • Serial Year
    2007
  • Journal title
    Energy
  • Record number