• Title of article

    Multiple-zone ventilation and temperature control of a single-duct VAV system using model predictive strategy

  • Author/Authors

    Shui Yuan، نويسنده , , Ronald Perez، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2006
  • Pages
    14
  • From page
    1248
  • To page
    1261
  • Abstract
    Conventional ventilation control schemes for VAV systems cannot achieve acceptable indoor air quality (IAQ). Ventilation control at the zone level is one of key factors affecting IAQ and also impacts thermal control. This paper proposes a multi-input–multi-output (MIMO) controller to control temperature and ventilation of multiple zones in a building with a model predictive control (MPC) strategy. The controller follows the ventilation rate procedure of ASHRAE Standard 62.1 and meets its ventilation requirements. Simulation-based experiments under four types of typical weather conditions are conducted to evaluate the controllerʹs performance. The experimental results demonstrate that the controller is capable of maintaining ventilation air requirements and temperature of multiple zones.
  • Keywords
    Multiple-zone ventilation , Model predictive control , VAV system
  • Journal title
    Energy and Buildings
  • Serial Year
    2006
  • Journal title
    Energy and Buildings
  • Record number

    419819