• Title of article

    Numerical study on temperature stratification in a room with underfloor air distribution system

  • Author/Authors

    Qiongxiang Kong، نويسنده , , Bingfeng Yu، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2008
  • Pages
    8
  • From page
    495
  • To page
    502
  • Abstract
    In this study, numerical prediction using computational fluid dynamics (CFD) was utilized to investigate air temperature stratification in a room with an underfloor air distribution (UFAD) system. The numerical modeling using CFD computation was validated with physical test in a full size experimental room with an UFAD system. The different supply air conditions and heat loads were discussed. The results show that the effect of three parameters, heat load, supply volume flux and supply air velocity, on room air temperature would be expressed by the length scale of the floor supply jet. When the length scale increased from 0.8 to 1.56 m, the ratio of vertical temperature difference between 2.5 and 0.1 m at the occupied zone to the difference between return and supply air temperature decreased from 0.62 to 0.25. When there was only one local heat source in the room, there was a thermal stratified interface at the occupied zone. The interface height was about 1.42 times the length scale. The results may suggest ways to optimize UFAD design and operation.
  • Keywords
    Temperature stratification , CFD , UFAD system , The length scale
  • Journal title
    Energy and Buildings
  • Serial Year
    2008
  • Journal title
    Energy and Buildings
  • Record number