Title of article :
Integration of distributed generation systems into generic types of commercial buildings in California
Author/Authors :
M. Medrano، نويسنده , , S. J. Brouwer، نويسنده , , V. McDonell، نويسنده , , J. Mauzey، نويسنده , , G. S. Samuelsen، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Pages :
12
From page :
537
To page :
548
Abstract :
Distributed generation (DG) of combined cooling, heat, and power (CCHP) has been gaining momentum in recent years as an efficient, secure alternative for meeting increasing power demands in the world. One of the most critical and emerging markets for DG-CCHP systems is commercial and institutional buildings. The present study focuses analysis on the main economic, energy-efficiency, and environmental impacts of the integration of three types of advanced DG technologies (high-temperature fuel cells, micro-turbines, and photovoltaic solar panels) into four types of representative generic commercial building templates (small office building, medium office building, hospital, and college/school) in southern California (e.g., mild climate), using eQUEST as energy simulation tool. Detailed load profiles for the four commercial building types during times of peak electric and peak gas consumption were analyzed and complementary strategies to further increase overall building energy efficiencies such as energy efficiency measures (e.g., day lighting, exterior shading, improved HVAC performance) and thermally activated absorption cooling were also investigated. Results show that the high-temperature fuel cell (HTFC) performance is best matched with the hospital energy loads, resulting in a 98% DG capacity factor, 85% DG heat recovery factor, and $860,000 in energy savings (6 years payback). The introduction of thermally driven double-effect absorption cooling (AC) in the college building with HTFC reduces significantly the building electricity-to-thermal load ratio and boosts the heat recovery factor from 37% to 97%.
Keywords :
Micro-turbine generators , Photovoltaic arrays , Emissions , Absorption cooling , load profiles , Building energy simulation , Distributed generation , fuel cells , Energy efficiency measures
Journal title :
Energy and Buildings
Serial Year :
2008
Journal title :
Energy and Buildings
Record number :
420042
Link To Document :
بازگشت