Title of article :
The use of a double heat pipe heat exchanger system for reducing energy consumption of treating ventilation air in an operating theatre—A full year energy consumption model simulation
Author/Authors :
Y.H. Yau، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Abstract :
In two earlier papers [Y.H. Yau, Application of a heat pipe heat exchanger to dehumidification enhancement in tropical HVAC systems—a baseline performance characteristics study, International Journal of Thermal Sciences 46 (2) (2007) 164–171; Y.H. Yau, The analysis of enthalpy change with and without a heat pipe heat exchanger in a tropical air conditioning system, International Journal of Energy Research 30 (15) (2006) 1251–1263], two series of experiments were conducted under controlled conditions to establish the baseline performance characteristics of the heat pipe heat exchanger (HPHX). In the present paper, a complete empirical transient systems simulation program model is assembled to estimate the air states as well as the entire typical meteorological year energy consumption of an operating theatre located in Kuala Lumpur, Malaysia.
Keywords :
Heat pipe heat exchanger , Energy savings , HVAC simulation , TRNSYS , Coolness recovery , Dehumidification
Journal title :
Energy and Buildings
Journal title :
Energy and Buildings