    Simulation and experimental validation of the variable-refrigerant-volume (VRV) air-conditioning system in EnergyPlus

  • Author/Authors

    Y.P. Zhou، نويسنده , , J.Y. Wu، نويسنده , , R.Z. Wang، نويسنده , , S. Shiochi، نويسنده , , Y.M. Li، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2008
  • Pages
    7
  • From page
    1041
  • To page
    1047
  • Abstract
    In order to evaluate the energy performance of the VRV air-conditioning system, a new simulation module is developed and validated experimentally in this study, on the basis of the building energy simulation program, EnergyPlus. The differences between average monitored and predicted data for the total cooling energy and power use are proved to be within 25.19% and 28.31%, respectively. Also, the relative error of power usage simulation follows that of cooling energy closely on an hourly basis. The COP and PLR simulation of the VRV system are also examined, with average error of 6.36% for COP and 18.40% for PLR. It is observed through the test that the energy performance of the VRV system at part-load condition is better than that in the rated condition.
  • Keywords
    Experiment , VRV system , simulation , EnergyPlus , validation