• Title of article

    Heating system performance estimation using optimization tool and BEMS data

  • Author/Authors

    Natasa Djuric، نويسنده , , Vojislav Novakovic، نويسنده , , Frode Frydenlund، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2008
  • Pages
    10
  • From page
    1367
  • To page
    1376
  • Abstract
    Causes and effects of a few real faults in a hydronic heating system are explained in this paper. Since building energy management system (BEMS) has to be utilized in fault detection and diagnosis (FDD), practical explanations of faults and their related effects are important to building caretakers. A simple heat balance model is used in this study. The model is calibrated using the optimization tool. Site data from the BEMS of a real building are calibrated against the model. Desired and real data are compared, so that the effects of the following faults are analyzed: faults in an outdoor air temperature sensor, fault in the time schedule, and a water flow imbalance problem. This paper presents an overview of the real causes of the faults and their effects both on the energy consumption and on the indoor air temperature. In addition, simple instructions for the building caretakers for fault detection in the hydronic heating systems are given.
  • Keywords
    Hydronic heating , optimization , Fault detection , model calibration
  • Journal title
    Energy and Buildings
  • Serial Year
    2008
  • Journal title
    Energy and Buildings
  • Record number

    420135