Title of article :
Spinning Reserve from Hotel Load Response
Author/Authors :
Brendan Kirby، نويسنده , , John Kueck، نويسنده , , Theo Laughner، نويسنده , , Keith Morris، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Pages :
8
From page :
59
To page :
66
Abstract :
Even though preliminary tests were not conducted during times of highest system or hotel loading during the summer, they showed that hotel load can be curtailed by 22 to 37 percent depending on the outdoor temperature and time of day. Full response occurred in 12 to 60 seconds from when the system operatorʹs command to shed load was issued and the load drop was very rapid.
Journal title :
The Electricity Journal
Serial Year :
2008
Journal title :
The Electricity Journal
Record number :
433397
Link To Document :
بازگشت