• Title of article

    Dependence of arc interrupting capability on spatial distribution of airflow velocity in air-blast flat-type quenching chamber

  • Author/Authors

    Y.، Yokomizu, نويسنده , , T.، Matsumura, نويسنده , , A.، Matsuda, نويسنده , , H، Ohno, نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    -100
  • From page
    101
  • To page
    0
  • Abstract
    The dependence of an interrupting capability on the spatial distribution of airflow velocity was investigated in an air-blast flat-type quenching chamber. To obtain a various distribution of airflow velocity, the axial position of a nozzle and the inlet width of the nozzle were varied. For each of the axial positions and each of the inlet widths, arc interruption tests for AC currents were performed to measure the interrupting capability. Furthermore, the distribution of airflow velocity in the quenching chamber was calculated intentionally in the absence of the arc. From the test and calculation results, we found out a definite relationship between the velocity distribution and the interrupting capability.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2003
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    61572