    Experience with return voltage measurements for assessing insulation conditions in service-aged transformers

  • Author/Authors

    T.K.، Saha, نويسنده , , Yao، Zheng Tong نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    -127
  • From page
    128
  • To page
    0
  • Abstract
    This paper describes the investigation of the insulation condition of a number of power and distribution type transformers of different manufacturing dates and with different operating histories. Return voltage measurements were conducted for these transformers. Effects of moisture and aging on the oil-paper insulation of these transformers were investigated and results are presented in this paper. Moisture in oil samples at known temperature was measured for these transformers. Previously accelerated aging experiments were performed on paper wrapped insulated conductors in different environments over a temperature range of 115 to 145/spl deg/C. Results from the measurements on transformers are compared with those of the accelerated aged samples and are described in this paper.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2003
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    61576