Title of article :
Power transformer temperature evaluation for overloading conditions
Author/Authors :
J.A.، Jardini, نويسنده , , J.L.P.، Brittes, نويسنده , , L.C.، Magrini, نويسنده , , M.A.، Bini, نويسنده , , J.، Yasuoka, نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
6
From page :
179
To page :
184
Abstract :
The calculation methodologies of transformersʹ hottest spot and top oil temperatures are evaluated in this paper. Thereafter, a comparison between the calculated and the values obtained during the assessment of a transformer factory test was realized. The referred tests were conducted using an ONAF type, 30/40 MVA, 138/13.8 kV transformer, in which sensors with fiber-optic cables, to record directly the internal parameters, were installed. In a first series of tests, transformer loadings corresponding to 100%, 70% and 116.5% of rated power, were used. The tests were completed by applying values of a daily load profile with several hourly power levels. Additionally, in two of the hourly periods, high temporary loadings one of 160% during 30 minutes, and another of 170% during 15 minutes, were applied.
Keywords :
Power-aware
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2005
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
61683
Link To Document :
بازگشت