Title of article
Improved detection of power transformer winding movement by extending the FRA high frequency range
Author/Authors
M.، Wang نويسنده , , A.J.، Vandermaar, نويسنده , , K.D.، Srivastava, نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
9
From page
1930
To page
1938
Abstract
FRA tests in the frequency range up to 10 MHz were investigated using simulations and measurements. It was found that the FRA test was more sensitive to changes in the transformer at frequencies above 1 to 3 MHz than at lower frequencies. However, the effects of the conventional test circuits mask the changes at the higher frequencies. A new test method is proposed that is effective up to at least 10 MHz.
Keywords
inner function , model , shift operator , Hilbert transform , admissible majorant , Hardy space , subspace
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2005
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
61891
Link To Document