Title of article :
Evaluation of Critical Clearing Time of Power System Equipped with a Static Synchronous Compensator
Author/Authors :
Prechanon Kumkratug D، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
6
From page :
141
To page :
146
Abstract :
Problem statement: The critical clearing time provides very important role of the robustness in power system. The Static Synchronous Compensator (STATCOM) has been accepted to be equipped in modern power system. This study presents the method to evaluate the Critical Clearing Time (CCT) of the system equipped with a Static Synchronous Compensator (STATCOM). Approach: The parameter on STATCOM is modeled in energy function. The presented energy function is applied to determine CCT of the system. The verification of the proposed method is tested on sample system. Results: The maximum generator rotor angle of the faulted system without a STATCOM is continuously oscillation and the maximum value is much more than the system with a STATCOM. Conclusion: STATCOM based the proposed nonlinear control can damp power system oscillation.
Keywords :
Power System Stability , FACTS devices , STATic synchronous COMpensator (STATCOM) , Energy function , voltage source , Single Machine Infinite Bus (SMIB) , voltage injection , Critical Clearing Time (CCT) , short circuit
Journal title :
American Journal of Applied Sciences
Serial Year :
2011
Journal title :
American Journal of Applied Sciences
Record number :
687830
Link To Document :
بازگشت