Title of article :
A new approach for indoor climate labeling of building materials—emission testing, modeling, and comfort evaluation
Author/Authors :
Peder Wolkoff، نويسنده , , Peter A. Nielsen، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Abstract :
A labeling system for building materialsʹ primary emission of volatile organic compounds (VOCs) according to their impact on comfort and health has been developed and introduced in Denmark. The system unifies chemical emission testing over time (months), modeling (including a standard room and mathematical modeling of the emission profile, when necessary), and health evaluation. As a first step, the Danish system focuses on comfort, i.e. odor annoyance and mucous membrane irritation, because of their preponderance in the sick building syndrome reporting and the absence of other relevant data on indoor air related health effects. Two design criteria have been set: the labeling system shall be easily comprehensible and at the same time operational and dynamic. The principle is to determine the time value, t(Cm), required to reach the relevant indoor air value, Cm (presently, based on odor and mucous membrane irritation thresholds), in a standard room. Odor thresholds are used because they generally are at least one order of magnitude lower than mucous membrane irritation thresholds. t(Cm) is a measure of the period of time during which a new building material may cause indoor air quality problems, unless special precautions are made. The system may also be used for singular VOCs of which a specific health endpoint has been reported. The Danish labeling system is illustrated with the emission testing and comfort evaluation of two sealants using the Field and Laboratory Emission Cell (FLEC)
Keywords :
Comfort. emission. building materials. health evaluation , labeling , MODELING , Indoor Air Quality , Volatile organic compounds (VOCs) , time value tiC m).
Journal title :
Atmospheric Environment
Journal title :
Atmospheric Environment