Title of article :
An experimental study on evaporative heat transfer coefficient and applications for passive cooling of AP600 steel containment Original Research Article
Author/Authors :
Y.M. Kang، نويسنده , , G.C. Park، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Pages :
13
From page :
347
To page :
359
Abstract :
After TMI and Chernobyl accidents, many efforts have been made to enhance the nuclear safety with passive features. Among such passive features, the passive containment cooling system (PCCS) has been suggested by Westinghouse in the AP600 plant. The containment with PCCS is a dual containment, and consists of a stainless steel vessel and a concrete wall. In the gap between these structures, air and water can counter-currently pass and cool the steel surface. This paper experimentally investigates evaporative heat and mass transfer at the surface of a falling water film with counter-current air flow in a vertical duct with one-side heated plate. Experiments included various conditions of mass flow rate of film and air. Experimental results show the strong effects of water temperature and air mass flow rate, but little effect of the water flow rate. Also, simple analyses based on heat and mass transfer analogy were performed to evaluate the experimental results. With experimental data, a new correlation on evaporative mass transfer coefficient was developed, and with the correlation, the containment pressure and temperature was calculated for the design basis accident of AP600 by the use of CONTEMPT4/MOD5 code implementation.
Journal title :
Nuclear Engineering and Design Eslah
Serial Year :
2001
Journal title :
Nuclear Engineering and Design Eslah
Record number :
889287
Link To Document :
بازگشت