• Title of article

    Experimental investigations on solar chimney for room ventilation

  • Author/Authors

    Jyotirmay Mathur، نويسنده , , *، نويسنده , , N.K. Bansal، نويسنده , , Sanjay Mathur، نويسنده , , Meenakshi Jain، نويسنده , , Anupma a، نويسنده ,

  • Issue Information
    ماهنامه با شماره پیاپی سال 2006
  • Pages
    9
  • From page
    927
  • To page
    935
  • Abstract
    Experimental investigations on a small size solar chimney show that the rate of ventilation increases with increase of the ratio between height of absorber and gap between glass and absorber. This finding is in agreement with results of the steady-state mathematical model developed for analysis of such systems. Nine different combination of absorber height and air gap have been investigated on the experimental set-up. Highest rate of ventilation induced with the help of solar energy was found to be 5.6 air change per hour in a room of 27 m3, at solar radiation 700 W/m2 on vertical surface with the stack height-air gap ratio of 2.83 for a 1 m high chimney. 2005 Elsevier Ltd. All rights reserved
  • Keywords
    Solar chimney , Air movement , Stack effect , Natural ventilation
  • Journal title
    Solar Energy
  • Serial Year
    2006
  • Journal title
    Solar Energy
  • Record number