Title of article
Experimental investigations on solar chimney for room ventilation
Author/Authors
Jyotirmay Mathur، نويسنده , , *، نويسنده , , N.K. Bansal، نويسنده , , Sanjay Mathur، نويسنده , , Meenakshi Jain، نويسنده , , Anupma a، نويسنده ,
Issue Information
ماهنامه با شماره پیاپی سال 2006
Pages
9
From page
927
To page
935
Abstract
Experimental investigations on a small size solar chimney show that the rate of ventilation increases with increase of the
ratio between height of absorber and gap between glass and absorber. This finding is in agreement with results of the
steady-state mathematical model developed for analysis of such systems. Nine different combination of absorber height
and air gap have been investigated on the experimental set-up. Highest rate of ventilation induced with the help of solar
energy was found to be 5.6 air change per hour in a room of 27 m3, at solar radiation 700 W/m2 on vertical surface with the
stack height-air gap ratio of 2.83 for a 1 m high chimney.
2005 Elsevier Ltd. All rights reserved
Keywords
Solar chimney , Air movement , Stack effect , Natural ventilation
Journal title
Solar Energy
Serial Year
2006
Journal title
Solar Energy
Record number
939660
Link To Document