Title of article
Modeling of water spray evaporation: Application to passive cooling of buildings
Author/Authors
Rafik Belarbi، نويسنده , , Cristian Ghiaus، نويسنده , , Francis Allard، نويسنده ,
Issue Information
ماهنامه با شماره پیاپی سال 2006
Pages
13
From page
1540
To page
1552
Abstract
The use of water droplet evaporation in shower towers and passive downdraft evaporative cooling needs the estimation
of the time needed to completely evaporate the drops. To solve this problem, a cellular approach is proposed in which the
spray is considered as a pile of rigid spheres of equal size; each sphere has multiple layers and contains a drop in its center.
The evaporation takes place gradually from the superficial layer towards the internal layers. Parametric studies show the
influence of each variable on the evaporation time o f the droplets. The model may be used for sizing passive evaporative
cooling systems and towers for buildings using the passive evaporative down draught effect. A building equipped with a
shower tower has been tested in the framework of the European project PDEC/JOULE in Catania (Italy). The spraying
system was successfully sized by using the model proposed in this paper.
2006 Published by Elsevier Ltd.