Title of article :
Sensitivity analysis of a maritime located night ventilated
library building
Author/Authors :
Donal P. Finn، نويسنده , , *، نويسنده , , Darragh Connolly b، نويسنده , , Paul Kenny c، نويسنده ,
Issue Information :
ماهنامه با شماره پیاپی سال 2007
Abstract :
An examination of the role of design and operational parameters in a night ventilated library building located in Ireland, and which is
subject to a maritime type climate, is considered. For this investigation, a self-contained space within the library building is analysed. A
dynamic model of the space is created using the ESPr simulation package, which is compared with building data obtained from an experimental
monitoring programme. Calculation of the mean bias deviation between the predicted and experimental data indicates agreement
better than 0.45 C for the dry bulb temperature and 1.1 C for the mean radiant temperature. Using ESPr predictions, the role of different
building design and operational parameters are examined by means of parametric analysis including building mass, ventilation
duration, internal gain and ventilation rates. Compared to a reference base of the existing building, increasing the building mass was
found to achieve a significant reduction in internal dry resultant temperatures, with a decrease of between 2 and 3 C observed when
mass was increased from 800 kg/m2 to 1600 kg/m2. Reducing building internal gains from 40 W/m2 to 20 W/m2 was observed to have
the potential of further reducing dry resultant temperatures by up to 1 C. Examination of night ventilation rates indicated that increasing
night ventilation up to 10 ACH was observed to have a significant affect on reduction of dry resultant temperature, but further
increases of air changes were observed to have a negligible effect.
2006 Elsevier Ltd. All rights reserved.
Keywords :
Night ventilation , Building sensitivity analysis , Maritime climate
Journal title :
Solar Energy
Journal title :
Solar Energy