• Title of article

    Research on ratio selection of a mixed liquid desiccant: Mixed LiCl–CaCl2 solution

  • Author/Authors

    Xiu-Wei Li *، نويسنده , , Xiao-Song Zhang، نويسنده , , Geng Wang، نويسنده , , Rong-Quan Cao، نويسنده ,

  • Issue Information
    ماهنامه با شماره پیاپی سال 2008
  • Pages
    11
  • From page
    1161
  • To page
    1171
  • Abstract
    Liquid desiccant cooling system is a new type of air-conditioning system capable of saving energy. The dehumidification process dominates the performance of this system, while the thermal properties of the liquid desiccant play a key role in improving dehumidification effect. However, there is little work about how to choose a proper liquid desiccant that has a better performance. To settle this problem, a novel method is proposed to search an ideal liquid desiccant by applying the nonrandom two-liquid equation (NRTL equation). This idea is further applied to mixed LiCl and CaCl2 solution to work out the right mixture ratio with a better dehumidification effect under certain working conditions. Moreover, the related experiments were carried out. The results show that: compared to single LiCl solution, the dehumidification effect could be raised by more than 20% with mixed LiCl and CaCl2 solution. 2008 Elsevier Ltd. All rights reserved
  • Keywords
    Mixed liquid desiccant , Dehumidification effect , Liquid-dehumidification , activity coefficient
  • Journal title
    Solar Energy
  • Serial Year
    2008
  • Journal title
    Solar Energy
  • Record number

    939993