Title of article :
Energy and economic performance analysis of an open cycle
solar desiccant dehumidification air-conditioning system for
application in Hong Kong
Author/Authors :
Yutong Li، نويسنده , , Lin Lu، نويسنده , , Hongxing Yang، نويسنده ,
Issue Information :
ماهنامه با شماره پیاپی سال 2010
Abstract :
In this article, a transient simulation model and the EnergyPlus were used to study the energy performance and economical feasibility
for integrating a solar liquid desiccant dehumidification system with a conventional vapor compression air-conditioning system for the
weather condition of Hong Kong. The vapor compression system capacity in the solar assisted air-conditioning system can be reduced to
19 kW from original 28 kW of a conventional air-conditioning system as a case study due to the solar desiccant cooling. The economical
performance of the solar desiccant dehumidification system is compared with that of the conventional air-conditioning system. The
results show that the energy saving potentials due to incorporation of the solar desiccant dehumidification system in a traditional airconditioning
system is significant for the hot wet weather in Hong Kong due to higher COP resulted from higher supply chilled water
temperature from chiller plants. The annual operation energy savings for the hybrid system is 6760 kWh and the payback period of the
hybrid system is around 7 years. The study shows that the solar assisted air-conditioning is a viable technology for utilizations in subtropical
areas.
2010 Elsevier Ltd. All rights reserved
Keywords :
Solar desiccant dehumidification , Energy performance , Economical analysis
Journal title :
Solar Energy
Journal title :
Solar Energy