Title of article :
Line-to-line short-circuit-based finite-element performance and parameter predictions of large hydrogenerators
Author/Authors :
R.، Wamkeue, نويسنده , , I.، Kamwa, نويسنده , , M.، Chacha, نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Pages :
9
From page :
370
To page :
378
Abstract :
A two-dimensional (2-D), time-stepped finite-element (FE) method is used to model and successfully replicate saturated line-toline and three-phase short-circuit test responses recorded on a 40-pole 13.75 MVA hydrogenerator at Hydro-Quebecʹs Rapides-des-Quinze generating station. Three levels of line-to-line and sudden three-phase short-circuit tests (0.13, 0.25, and 0.48 p.u.) are simulated numerically using the FE-based model. While symmetrical faults are only used for parameter determination, the computed line-to-line waveforms are thoroughly compared to real data, with special attention given to field current responses. According to IEEE Std.-115-1995, the d-axis dynamic reactances and time-constants are computed from three-phase short-circuit tests while the negative-sequence reactance is derived from the line-to-line short-circuit test resulting in a rated armature current. The obtained simulated tests responses and parameter values, from both symmetrical and asymmetrical faults, support the effectiveness of the proposed FE-based model in incorporating the saturation phenomenon, large number of poles, and detailed damper representation to achieve an accurate dynamic performance assessment together with negativesequence reactance and dynamic constants prediction.
Keywords :
Power-aware
Journal title :
IEEE Transactions on Energy Conversion
Serial Year :
2003
Journal title :
IEEE Transactions on Energy Conversion
Record number :
98505
Link To Document :
بازگشت