Energy and Exergy Analysis of Double Effect LiCl/H2O Absorption Refrigeration Cycle and Comparison with LiBr/H2O Cycle
Author/Authors :
A Akbari Sula Faculty of Mechanical Engineering - Tarbiat Modares University, Tehran, Iran , L Garousi Farshib Faculty of Mechanical Engineering - University of Tabriz, Tabriz, Iran
كليدواژه :
Energy , Exergy , Series Flow , Double Effect Absorption
عنوان كنفرانس :
ششمين كنفرانس ملي ساليانه انرژي پاك
چكيده لاتين :
Series flow double effect LiCl/H2O absorption refrigeration system is analyzed
thermodynamically and compared with similar system using LiBr aqueous solution
as a working pair. The simulations for LiCl/H2O system are carried out via EES
software and the properties provided for materials in the EES database are utilized.
Energy and exergy considerations of LiBr/H2O system have been investigated
previously. The results of the simulation and data from previous studies are
compared, and then advantages and disadvantages of mentioned systems are
indicated. These examinations would be useful in the design and control of such
systems. The comparison demonstrates wider operational range of water-LiBr
system at various generator temperatures rather than water-LiCl system, whereas
maximum obtainable COP and exergetic efficiency is much higher for water-LiCl
system. Moreover the LiCl/H2O system operates in much lower pressure levels.