• DocumentCode
    1000916
  • Title

    Lightning Investigation on Transmission Lines---III

  • Author

    Lewis, W.W. ; Foust, C.M.

  • Author_Institution
    General Electric Company, Schenectady, N. Y.
  • Volume
    52
  • Issue
    2
  • fYear
    1933
  • fDate
    6/1/1933 12:00:00 AM
  • Firstpage
    475
  • Lastpage
    480
  • Abstract
    The field data for 1931 and 1932 are reviewed, with especial reference to lightning stroke currents. When direct strokes take place to towers or ground wires, flashover occurs if the product of current and tower footing resistance is higher than the fiashover strength of the insulators. Flashover seldom occurs if ground wires are present and the towers have low footing resistance. Three years´ records on four systems indicate tower currents varying from 1,000 to 150,000 amperes. Tripouts correlate almost exclusively with high tower leg currents of negative polarity, that is, the tower top is negative with respect to the base. This indicates that the severe lightning strokes come from negatively charged clouds. A great amount of experimental data, relating to flashover between electrodes of dissimilar shapes, are shown to be in accord with these field observations.
  • Keywords
    Cable insulation; Conductors; Flashover; Instruments; Lightning; Poles and towers; Surges; Wires;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1933.5056333
  • Filename
    5056333