DocumentCode
1000963
Title
Application of numeric protective relay circuit breaker duty monitoring
Author
Dalke, Gerald ; Horak, John
Author_Institution
Basler Electr. Co., Edmond, OK, USA
Volume
41
Issue
4
fYear
2005
Firstpage
1118
Lastpage
1124
Abstract
Most numeric or digital protective overcurrent systems on the market today state that they have some ability to provide an indication, based on parameters that are input by the user, that circuit breaker maintenance may be needed soon. This paper will look at variables in a protective relay´s ability to provide the user with an indication of its associated circuit breaker´s health based upon the amount of current the circuit breaker has interrupted and the associated energy dissipation in the circuit breaker contact surfaces. The variables in an arc energy formula will be examined and the complications related to estimating the associated wear or circuit breaker duty level from interrupted current will be reviewed. Practical examples will include calculations of circuit breaker wear at load currents and for full rated fault interruptions.
Keywords
circuit breakers; condition monitoring; maintenance engineering; overcurrent protection; relay protection; circuit breaker maintenance; contact surfaces; digital protective overcurrent systems; duty monitoring; energy dissipation; numeric protective relay circuit breaker; Cause effect analysis; Circuit breakers; Circuit faults; Condition monitoring; Digital relays; History; Industry Applications Society; Manufacturing; Protection; Protective relaying; Circuit breaker; circuit breaker wear; duty level; monitoring; numeric relay;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2005.851568
Filename
1468291
Link To Document