• DocumentCode
    1002234
  • Title

    Short-circuit effects in HV substations with strained conductors-systematic full scale tests and a simple calculation method

  • Author

    Herrmann, B. ; Stein, N. ; Kiessling, G.

  • Author_Institution
    FGH Forschungsgemeinschaft fur Hochspannungs und Hochstromtechnik, Mannheim, West Germany
  • Volume
    4
  • Issue
    2
  • fYear
    1989
  • fDate
    4/1/1989 12:00:00 AM
  • Firstpage
    1021
  • Lastpage
    1028
  • Abstract
    The dynamic short-circuit stresses in HV (high-voltage) substations with flexible conductors are determined by a large number of parameters. Tensile forces, stresses, and conductor displacements have been studied for short-circuit currents of 20-40 kA (RMS) in test arrangements representing strained conductors of typical 123 kV and 420 kV substations at a span length of 40 m. A simple calculation method based on the approach of IEC Publication 865 and DIN VDE 0103, but taking the short-circuit duration into account, has been developed, leading to reduced forces and displacements in the case of brief current flow
  • Keywords
    conductors (electric); short-circuit currents; substations; 123 kV; 20 to 40 kA; 420 kV; DIN VDE 0103; HV substations; IEC Publication 865; conductor displacements; dynamic short-circuit stresses; short-circuit currents; strained conductors; tensile forces; Application software; Conductors; Finite element methods; IEC standards; Standards publication; Steel; Stress; Substations; Suspensions; System testing;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.25582
  • Filename
    25582