    Post-arc current in high voltage SF6 circuit-breakers when breaking at up to 63 kA

  • Author

    Blez, B. ; Guilloux, C.

  • Author_Institution
    Electr. de France, Paris, France
  • Volume
    4
  • Issue
    2
  • fYear
    1989
  • fDate
    4/1/1989 12:00:00 AM
  • Firstpage
    1056
  • Lastpage
    1062
  • Abstract
    Post-arc current measurements were made on a high-voltage SF6 circuit breaker. A pyrotechnic device was used to protect the measurement shunt. The tests, performed at high current values between 40 and 63 kA, gave post-arc current levels of 0.5 to 2 A. Interpretation of the experimental results by the generalized Mayr model led to the determination of a set of parameters characteristic of the apparatus tested, thereby making it possible to find the test results and, in particular, to forecast cases of thermal failure
  • Keywords
    circuit breakers; electric current measurement; gaseous insulation; sulphur compounds; 0.5 to 2 A; 40 to 63 kA; HV circuit breakers; SF6 circuit breakers; generalized Mayr model; post arc current measurement; Bandwidth; Circuit testing; Current measurement; IEC standards; Laboratories; Performance evaluation; Power measurement; Protection; Sulfur hexafluoride; Voltage;