Title :
Development of insulation technology for high-voltage gas-insulated transformer
Author :
Goto, K. ; Yamazaki, T. ; Teranishi, T. ; Ikeda, M. ; Murase, H. ; Ukobo, H.
Author_Institution :
Tokyo Electr. Power Co. Inc., Tokyo, Japan
fDate :
4/1/1989 12:00:00 AM
Abstract :
Insulation technology development for 275 kV 300 MVA class SF6 gas-insulated transformers is described. The main area of development is turn-to-turn insulation using polymer film in sheeting winding. It was experimentally demonstrated that two sheets of film, several tens of micrometer in thickness, had sufficient insulation strength for impulse and short/long-term AC voltage application. Sufficient insulation performance for coil end insulation was demonstrated by a full-scale impulse model, taking into consideration the results of three-dimensional electric field analysis. A 275 kV 50 MVA prototype with an insulation structure equivalent to that of 275 kV 300 MVA units was developed, and a three-month reliability test was conducted
Keywords :
gaseous insulation; power transformers; reliability; sulphur compounds; transformer insulation; transformer testing; 275 kV; 300 MVA; 3D electric field analysis; HV gas-insulated transformers; SF6 insulated transformers; polymer sheet winding; reliability test; turn-to-turn insulation; Coils; Dielectrics and electrical insulation; Electric fields; Gas insulation; Insulation testing; Performance analysis; Plastic insulation; Polymer films; Power transformer insulation; Prototypes;
Journal_Title :
Power Delivery, IEEE Transactions on