• DocumentCode
    1004783
  • Title

    Calibration of the Sphere Gap

  • Author

    Meador, J.R.

  • Author_Institution
    General Elec. Co. Pittsfield, Mass.
  • Volume
    53
  • Issue
    6
  • fYear
    1934
  • fDate
    6/1/1934 12:00:00 AM
  • Firstpage
    942
  • Lastpage
    948
  • Abstract
    A series of sparkover voltage calibration tests on sphere gaps using spheres of various sizes up to 200 cm in diameter are reported in this paper. Tests were made with gap spacings ordinarily used in pratice, and with 60-cycle and both positive and negative impulse voltages. Since these tests as well as those of other investigators show that some of the A.I.E.E. standard sphere gap calibration curves are in error, it is recommended that those standards be revised. Recommendations are made for the adoption of separate calibration curves for positive and negative impulses and for correcting the 60-cycle calibration curves of large spheres.
  • Keywords
    Calibration; Density measurement; Dielectrics and electrical insulation; Frequency measurement; Gas insulation; Insulator testing; Temperature;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1934.5056753
  • Filename