Performance of a long-time unattended station for measuring DC fields and air ions from an operating HVDC line
Author
Chartier, V.L. ; Dickson, L.D. ; Lee, L.Y. ; Stearns, R.D.
Author_Institution
Bonneville Power Adm., Vancouver, WA, USA
Volume
4
Issue
2
fYear
1989
fDate
4/1/1989 12:00:00 AM
Firstpage
1318
Lastpage
1328
Abstract
The authors describe the experience of the Bonneville Power Administration in building and operating a long-term, unattended station to measure electric fields and air ions from the Pacific NW/SW HVDC (northwest/southwest high-voltage direct current) Intertie. The major emphasis is on the performance of the unipolar ion counters, as these have been the most difficult type of instrument to incorporate in an outdoor measurement station. Based on this experience, if heat is properly applied to the ion counter and good procedures are used for regular calibration and maintenance of all the instrumentation, then electric field and air ion instrumentation can be operated unattended in an outdoor environment
Keywords
electric field measurement; power overhead lines; power system interconnection; test facilities; Bonneville Power Administration; DC field measurement; Pacific NW/SW HVDC Intertie; air ions measurement; calibration; unipolar ion counters; Conductors; Corona; Counting circuits; Electric variables measurement; HVDC transmission; Instruments; Power measurement; Space charge; System testing; Voltage;