DocumentCode :
1005227
Title :
Study on reduction in electric field, charged voltage, ion current and ion density under HVDC transmission lines by parallel shield wires
Author :
Amano, Yuji ; Sunaga, Yoshitaka
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
Volume :
4
Issue :
2
fYear :
1989
fDate :
4/1/1989 12:00:00 AM
Firstpage :
1351
Lastpage :
1359
Abstract :
Several models of shield wire were tested with the Shiobara HVDC (high-voltage direct current) test line. The models contain typical standard wires that are generally used to reduce field effects at ground level, neutral conductors placed at lower parts of the DC line, and an earth corona model to intentionally cancel positive or negative ions by generating ions having opposite polarity to ions flowing into the wire. The authors describe experimental results on the effects of these shield wires and a method to predict shielding effects. It is concluded that shielding using the earth corona is quite an effective method; it is even applicable to the reduction of ion density, which has normally been considered difficult
Keywords :
corona; electric fields; ion density; power overhead lines; shielding; HVDC transmission lines; charged voltage reduction; earth corona model; electric field reduction; ion current reduction; ion density reduction; neutral conductors; parallel shield wires; Circuit testing; Conductors; Corona; Current density; Electric shock; Electric variables measurement; HVDC transmission; Power transmission lines; Voltage; Wires;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.25622
Filename :
25622
Link To Document :
بازگشت