Telephone interference criteria for HVDC transmission lines
Author :
Johansson, Arne V. ; Ekstrom, Ake
Author_Institution :
ASEA Brown Boveri AB, Ludvika, Sweden
Volume :
4
Issue :
2
fYear :
1989
fDate :
4/1/1989 12:00:00 AM
Firstpage :
1408
Lastpage :
1421
Abstract :
The coupling between a transmission line and telephone cables is calculated on a general basis. Based on field measurements of the current harmonic spectrum from a modern 12-pulse HVDC (high-voltage direct current) converter, the ratio between disturbance current and resulting noise level in a telephone system is established. Disturbance current limitation criteria are identified based on tolerable noise level and assumptions regarding typical worst-case coupling conditions in a suburban area between a transmission line and a telephone system. It is concluded that disturbance current criteria as currently specified for some HVDC lines are substantially more stringent than corresponding criteria for both distribution lines and HVAC (high-voltage alternating current) lines
Keywords :
interference (signal); power transmission lines; telephone lines; 12-pulse HVDC convertor; HVDC transmission lines; current harmonic spectrum measurements; disturbance current criteria; telephone cable interference; worst-case coupling conditions; Cables; Couplings; Current measurement; HVDC transmission; Interference; Noise level; Noise measurement; Telephony; Transmission line measurements; Transmission lines;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.25628
Filename :
25628
Link To Document :
بازگشت