• DocumentCode
    1005818
  • Title

    Telephone interference criteria for HVDC transmission lines

  • Author

    Johansson, Arne V. ; Ekstrom, Ake

  • Author_Institution
    ASEA Brown Boveri AB, Ludvika, Sweden
  • Volume
    4
  • Issue
    2
  • fYear
    1989
  • fDate
    4/1/1989 12:00:00 AM
  • Firstpage
    1408
  • Lastpage
    1421
  • Abstract
    The coupling between a transmission line and telephone cables is calculated on a general basis. Based on field measurements of the current harmonic spectrum from a modern 12-pulse HVDC (high-voltage direct current) converter, the ratio between disturbance current and resulting noise level in a telephone system is established. Disturbance current limitation criteria are identified based on tolerable noise level and assumptions regarding typical worst-case coupling conditions in a suburban area between a transmission line and a telephone system. It is concluded that disturbance current criteria as currently specified for some HVDC lines are substantially more stringent than corresponding criteria for both distribution lines and HVAC (high-voltage alternating current) lines
  • Keywords
    interference (signal); power transmission lines; telephone lines; 12-pulse HVDC convertor; HVDC transmission lines; current harmonic spectrum measurements; disturbance current criteria; telephone cable interference; worst-case coupling conditions; Cables; Couplings; Current measurement; HVDC transmission; Interference; Noise level; Noise measurement; Telephony; Transmission line measurements; Transmission lines;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.25628