• DocumentCode
    1005889
  • Title

    Availability of corona cage for predicting audible noise generated from HVDC transmission line

  • Author

    Nakano, Yukio ; Sunaga, Yoshitaka

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
  • Volume
    4
  • Issue
    2
  • fYear
    1989
  • fDate
    4/1/1989 12:00:00 AM
  • Firstpage
    1422
  • Lastpage
    1431
  • Abstract
    The authors examine the feasibility of using a corona cage to predict audible noise (AN) generated from an HVDC (high-voltage direct current) transmission line. The possible use of the cage is based on the assumption that generation quantities of AN and corona current are determined by Fmax (the `true´ maximum conductor surface gradient in the presence of space charge) regardless of the surrounding electrode arrangement. This assumption has been verified by tests using corona cages and a test line. The results indicate that a corona cage is indeed suitable for predicting AN generated from HVDC transmission lines. It is applicable to DC lines with any line configuration and any polarity arrangement
  • Keywords
    acoustic noise measurement; corona; power overhead lines; HVDC transmission line; audible noise prediction; corona cage; power overhead lines; Acoustic noise; Availability; Conductors; Corona; DC generators; Electrodes; HVDC transmission; Space charge; Testing; Transmission lines;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.25629
  • Filename
    25629