DocumentCode :
1005889
Title :
Availability of corona cage for predicting audible noise generated from HVDC transmission line
Author :
Nakano, Yukio ; Sunaga, Yoshitaka
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
Volume :
4
Issue :
2
fYear :
1989
fDate :
4/1/1989 12:00:00 AM
Firstpage :
1422
Lastpage :
1431
Abstract :
The authors examine the feasibility of using a corona cage to predict audible noise (AN) generated from an HVDC (high-voltage direct current) transmission line. The possible use of the cage is based on the assumption that generation quantities of AN and corona current are determined by Fmax (the `true´ maximum conductor surface gradient in the presence of space charge) regardless of the surrounding electrode arrangement. This assumption has been verified by tests using corona cages and a test line. The results indicate that a corona cage is indeed suitable for predicting AN generated from HVDC transmission lines. It is applicable to DC lines with any line configuration and any polarity arrangement
Keywords :
acoustic noise measurement; corona; power overhead lines; HVDC transmission line; audible noise prediction; corona cage; power overhead lines; Acoustic noise; Availability; Conductors; Corona; DC generators; Electrodes; HVDC transmission; Space charge; Testing; Transmission lines;