DocumentCode :
1006508
Title :
Discharge Currents in Distribution Arresters
Author :
McEachron, K.B. ; McMorris, W.A.
Author_Institution :
General Electric Company, Pittsfield, Mass.
Volume :
54
Issue :
12
fYear :
1935
Firstpage :
1395
Lastpage :
1399
Abstract :
With a view to augmenting the meager data available on the discharge currents through lightning arresters on electric power distribution circuits, the investigation reported in this paper, which covered 4 power systems of various voltages and in different sections of the country, was undertaken. Over the range of circuit voltages involved rating seemed to have(4 to 24 kv) voltage on the discharges. More negative than positive discharges were recorded, the ratio increasing as the discharge current increased. The maximum current recorded was 17,000 amperes.
Keywords :
Arresters; Differential equations; Fault location; Insulation; Lightning; Synchronous machines; Synchronous motors;
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
Publisher :
ieee
ISSN :
0096-3860
Type :
jour
DOI :
10.1109/T-AIEE.1935.5056936
Filename :
5056936