DocumentCode
1006853
Title
Flashover Performance of HVDC Iced Insulator Strings
Author
Li, Peng ; Fan, Jianbin ; Li, Wufeng ; Su, Zhiyi ; Zhou, Jun
Author_Institution
China Electr. Power Res. Inst., Beijing
Volume
14
Issue
6
fYear
2007
fDate
12/1/2007 12:00:00 AM
Firstpage
1334
Lastpage
1338
Abstract
Based on artificial icing test results, it was found that the DC flashover voltage of iced insulator strings was non-linear with different string lengths. An experimental formula of flashover voltage on iced insulators of different string lengths is introduced in this paper. Icing tests were carried out on different kinds of insulators including DC anti-fog, double-shed and three-shed insulators. Under serious ice conditions, the DC flashover voltages of the different types of insulator strings were very close. The flashover voltage of energized iced strings was a little higher than that of de-energized ones.
Keywords
HVDC power transmission; flashover; insulators; power cable insulation; DC antifog insulator; HVDC iced insulator string; artificial icing test; double-shed insulator; flashover voltage; three-shed insulator; Africa; Conductivity; Dielectrics and electrical insulation; Flashover; HVDC transmission; Ice; Insulator testing; Power industry; USA Councils; Voltage;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2007.4401215
Filename
4401215
Link To Document