• DocumentCode
    1006853
  • Title

    Flashover Performance of HVDC Iced Insulator Strings

  • Author

    Li, Peng ; Fan, Jianbin ; Li, Wufeng ; Su, Zhiyi ; Zhou, Jun

  • Author_Institution
    China Electr. Power Res. Inst., Beijing
  • Volume
    14
  • Issue
    6
  • fYear
    2007
  • fDate
    12/1/2007 12:00:00 AM
  • Firstpage
    1334
  • Lastpage
    1338
  • Abstract
    Based on artificial icing test results, it was found that the DC flashover voltage of iced insulator strings was non-linear with different string lengths. An experimental formula of flashover voltage on iced insulators of different string lengths is introduced in this paper. Icing tests were carried out on different kinds of insulators including DC anti-fog, double-shed and three-shed insulators. Under serious ice conditions, the DC flashover voltages of the different types of insulator strings were very close. The flashover voltage of energized iced strings was a little higher than that of de-energized ones.
  • Keywords
    HVDC power transmission; flashover; insulators; power cable insulation; DC antifog insulator; HVDC iced insulator string; artificial icing test; double-shed insulator; flashover voltage; three-shed insulator; Africa; Conductivity; Dielectrics and electrical insulation; Flashover; HVDC transmission; Ice; Insulator testing; Power industry; USA Councils; Voltage;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2007.4401215
  • Filename
    4401215