DocumentCode :
1007099
Title :
A Criterion of Quality of Cable Insulation
Author :
Wyatt, K.S. ; Spring, E.W.
Author_Institution :
The Detroit (Mich.) Edison Co.
Volume :
54
Issue :
4
fYear :
1935
fDate :
4/1/1935 12:00:00 AM
Firstpage :
417
Lastpage :
421
Abstract :
Radial uniformity of oil impregnated paper cable insulation, that is, uniformity in a radial direction from conductor to sheath, is a characteristic of well manufactured cable that is fully as important or more so than longitudinal uniformity. Radial power factor curves for several brands of new cable included in this paper show marked irregularities which are attributed to poorly controlled manufacturing methods. On the basis of such studies, some manufacturers have made efforts to improve the radial uniformity of their insulation with resulting great improvement in quality. This characteristic of cable insulation thus provides a criterion of insulation quality that should be useful to both manufacturer and user.
Keywords :
Cable insulation; Cable shielding; Conductors; Power cable insulation; Power cables; Power measurement; Reactive power;
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
Publisher :
ieee
ISSN :
0096-3860
Type :
jour
DOI :
10.1109/T-AIEE.1935.5056999
Filename :
5056999
Link To Document :
بازگشت