• DocumentCode
    1010117
  • Title

    On-load test of the 20kVA superconducting generator

  • Author

    Okada, T. ; Nitta, T. ; Shintani, T.

  • Author_Institution
    Kyoto University, Yoshida-honmachi Sakyo-ku Kyoto, Japan
  • Volume
    21
  • Issue
    2
  • fYear
    1985
  • fDate
    3/1/1985 12:00:00 AM
  • Firstpage
    668
  • Lastpage
    671
  • Abstract
    The on-load tests are carried out on an experimental power system, where the 20 kVA superconducting synchronous generator is connected to the regional power system through reactors (artificial transmission lines). The cooling characteristics of the rotor, especially, the cold damper, are obtained. On the on-load tests, active power vs. reactive power, active power vs. load angle, field current vs. active power characteristics at the constant terminal voltage, and so on are obtained. The transient behavior of the generator for a small variation of the input power is obtained. A transient analysis for the above test was carried out. Good agreement between the measured and calculated values is confirmed. From the results, the characteristics of superconducting generators are compared with those of the conventional ones and discussed.
  • Keywords
    Rotating machine testing; Superconducting rotating machines; Synchronous generators; Cooling; Inductors; Power system transients; Power systems; Power transmission lines; Reactive power; Rotors; Superconducting transmission lines; Synchronous generators; System testing;
  • fLanguage
    English
  • Journal_Title
    Magnetics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9464
  • Type

    jour

  • DOI
    10.1109/TMAG.1985.1063807
  • Filename
    1063807