DocumentCode :
1011626
Title :
Modeling of emergency diesel generators in an 800 megawatt nuclear power plant
Author :
Yeager, K.E. ; Willis, J.R.
Author_Institution :
Consumers Power Co., Jackson, MI, USA
Volume :
8
Issue :
3
fYear :
1993
fDate :
9/1/1993 12:00:00 AM
Firstpage :
433
Lastpage :
441
Abstract :
Computer models have been developed of emergency diesel generators and their associated emergency core cooling system induction motors during sequencing and results compared with field tests. Models required to perform studies of emergency diesel generators in a nuclear plant are presented. Field measurements indicating different response of two seemingly identical generator excitation systems are discussed. Results of 480 volt AC contactor dropout testing are provided for determining voltage limits in the 480 volt system during motor starting transients
Keywords :
contactors; diesel-electric generators; fission reactor cooling and heat recovery; fission reactor safety; fission reactor theory and design; induction motors; machine theory; nuclear power stations; standby generators; starting; transients; 480 V; 800 MW; AC contactor dropout testing; emergency core cooling system; emergency diesel generators modelling; field tests; generator excitation systems; induction motors; motor starting transients; nuclear power plant; sequencing; voltage limits determination; Cooling; Emergency power supplies; Induction generators; Induction motors; Nuclear power generation; Power generation; Power system modeling; Propagation losses; System testing; Voltage;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/60.257056
Filename :
257056
Link To Document :
بازگشت