Title :
Probable Outages of Shielded Transmission Lines
Author_Institution :
Engineer for the Pennsylvania Water & Power Company, Baltimore, Md.
fDate :
5/1/1937 12:00:00 AM
Abstract :
Based on the observed phenomenon that flashover of transmission-line towers provided with 2 overhead ground wires occurs only when the product of tower footing resistance and tower surge current exceeds the insulation strength, the probable outages that will occur on a line can be obtained by a simple method. Only those factors enter into the calculations which have become generally accepted quantitatively. Computations have been made for 3 transmission lines and the results compared with operating records. The agreement has been very good.
Keywords :
Cable insulation; Conductors; Flashover; Lightning; Poles and towers; Power overhead lines; Power system faults; Power system restoration; Surges; Transmission lines;
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
DOI :
10.1109/T-AIEE.1937.5057601