DocumentCode :
1013705
Title :
Double-Line-to-Neutral Short Circuit of an Alternator
Author :
Smith, James B. ; Weygandt, Cornelius N.
Author_Institution :
Associated Factory Mutual Fire Insurance Companies, Boston, Mass.
Volume :
56
Issue :
9
fYear :
1937
Firstpage :
1149
Lastpage :
1155
Abstract :
Starting with R. H. Park´s formulas for the flux linkages of an ideal synchronous machine, the case of a fault from 2 line terminals of a generator to neutral is treated in a manner similar to that used by Doherty and Nickle for other unsymmetrical faults. Expressions are given for the armature currents in the faulted phases and for the main field current, at any time after the short circuit. An expression for the voltage across the open phase a short time after the fault is also developed.
Keywords :
Alternators; Circuit faults; Couplings; Equations; Inductance; Synchronous generators; Synchronous machines; Voltage control;
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
Publisher :
ieee
ISSN :
0096-3860
Type :
jour
DOI :
10.1109/T-AIEE.1937.5057707
Filename :
5057707
Link To Document :