Abstract :
The life of cellulose insulation in oil has been investigated as a function of temperature under conditions of free access to oxygen and also in an inert atmosphere. Temperatures up to 140 degrees centigrade have been used. An attempt has been made also to study the life of oils as a function of oxygen concentration in an actual transformer at various temperatures. The amount of oxygen to produce a given acidity was also determined. On the basis of these data on oils, an attempt has been made to calculate rates of oxygen absorption by oil which may be used to estimate the relative deterioration in transformers of other dimensions. The results show cellulose deteriorates only mechanically, retaining its electrical properties. It is subject to both temperature and oxidation effects, the temperature effect, of course, taking place above 105 degrees centigrade.
Keywords :
Atmosphere; Dielectric liquids; Heat transfer; Oil insulation; Oxidation; Power transformer insulation; Temperature measurement;