Voltage Sags and the Response of a Synchronous Distributed Generator: A Case Study
Author :
Collins, E.R. ; Jian Jiang
Author_Institution :
Clemson Univ., Clemson
Volume :
23
Issue :
1
fYear :
2008
Firstpage :
442
Lastpage :
448
Abstract :
The dynamic behavior of a synchronous distributed generator connected to a distribution system during fault conditions is studied. A fault on an actual system was found to have a sag that was extended after the fault was cleared. It is shown that the combination of the generator and the load on the system contributes to the extended sag. The detailed simulation studies demonstrate that the primary factors are the reactive power drawn by the load during the fault and recovery along with the reaction of the generator. The prediction of such behavior requires proper modeling of the generator, the generator´s controls, and the system and dynamic load. Operators of such generators need to be aware of this type of system and load response when synchronous DG is connected to a distribution network.
Keywords :
distribution networks; power supply quality; power system faults; synchronous generators; voltage regulators; distributed generation; distribution network; distribution system; dynamic load; excitation controls; fault analysis; fault conditions; generator controls; load response; power quality; reactive power; synchronous distributed generator; system load; voltage regulator; voltage sags; Circuit faults; Power generation; Power quality; Power system modeling; Reactive power; Reactive power control; Standby generators; Synchronous generators; Transformers; Voltage; Distributed generation (DG); distribution systems; excitation controls; fault analysis; power quality (PQ); voltage regulator; voltage sags;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2007.905562
Filename :
4408676
Link To Document :
بازگشت