• DocumentCode
    1021715
  • Title

    A New One-Cycle Directional Overcurrent Relay

  • Author

    Morris, W.C.

  • Author_Institution
    Design engineer, relay department, General Electric Company, Philadelphia, Pa.
  • Volume
    62
  • Issue
    11
  • fYear
    1943
  • Firstpage
    725
  • Lastpage
    727
  • Abstract
    This paper describes a new one-cycle directional overcurrent relay which is not limited in its application by lack of contact co-ordination. That contact coordination is important is indicated by the many incorrect relay operations which have been traced to the common practice of adding instantaneous attachment to directional overcurrent relays. For years it has been known that directional control is not sufficient for instantaneous directional over-current relays. This paper describes a new application of ``memory action´´ which for the first time complements directional control to give always correct operation. The new idea is to use ``memory action´´ to obtain a time delay in the operation of the overcurrent unit in the order of one-half cycle. Of course ``memory action´´ is also used in the directional element to retain a high torque level even if the fault causes drastic voltage reduction. Both elements are of the rugged induction cylinder.
  • Keywords
    Circuit breakers; Circuit faults; Delay effects; Fault currents; Power system relaying; Power system stability; Protection; Protective relaying; Relays; Torque;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1943.5058637
  • Filename
    5058637