DocumentCode
1027086
Title
Wet tests under AC voltage and switching impulses procedure and significant parameters
Author
Riu, J.P. ; Hutzler, B. ; Rowe, S.W. ; Huc, J. ; Maurin, P.
Author_Institution
Electricite de France, Paris, France
Volume
3
Issue
1
fYear
1988
fDate
1/1/1988 12:00:00 AM
Firstpage
298
Lastpage
306
Abstract
The lack of reproducibility of wet tests, especially under AC voltage, has been a critical problem for acceptance tests or sampling tests. For this reason a task force was established to improve the wet-test procedure. The test program is described. The role played by the precipitation distribution along the insulator is demonstrated, and consequences for rain intensity measurements and requirements are drawn with respect to the IEC Publication 60 revision. Data on the dielectric strength of post insulators under switching impulses are given for design purposes
Keywords
electric strength; insulators; testing; AC voltage; IEC Publication 60 revision; dielectric strength; insulator; post insulators; precipitation distribution; rain intensity measurements; switching impulses; wet tests; Dielectric breakdown; Dielectric measurements; Dielectrics and electrical insulation; IEC standards; Impulse testing; Insulator testing; Laboratories; Proposals; Rain; Reproducibility of results; Sampling methods; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.4257
Filename
4257
Link To Document